Circuits, Three-Phase Power and Electrical Measurements — ESE Electrical
Weightage: Circuit theory and measurements open the Electrical papers and feed every later chapter. Questions are short numerical items on theorems, resonance, three-phase power and instrument ranges, and most can be answered in a minute when the standard result is known.
1. Network theorems
Kirchhoff's laws are the basis: the algebraic sum of currents at a node is zero, and the sum of voltages around a loop is zero.
- Thevenin: a linear two-terminal network is equivalent to a voltage source (the open-circuit voltage) in series with (the resistance seen with sources deactivated).
- Norton: the same network is a current source in parallel with .
- Superposition: in a linear circuit, the response is the sum of responses to each source acting alone. Voltage sources are shorted and current sources opened when inactive. It does not apply to power.
- Maximum power transfer: a load receives maximum power when , and the power is . For AC the load impedance must be the complex conjugate of the source impedance.
Worked example. A source has V and . The maximum power is W at , with an efficiency of only 50 percent.
Reciprocity holds for linear passive networks, and Tellegen's theorem says the sum of power absorbed by all branches is zero.
2. Transients
A first-order circuit responds exponentially with time constant for RL and for RC. After one time constant a charging capacitor reaches 63.2 percent of its final voltage, and after five time constants the response is practically complete.
At : an inductor keeps its current continuous (it acts as an open circuit for a step if the initial current is zero), and a capacitor keeps its voltage continuous (it acts as a short circuit if uncharged).
For a series RLC circuit, the damping condition is set by compared with . A larger gives an overdamped response, equality gives critical damping, and a smaller gives an underdamped, oscillatory response.
3. Resonance
A series RLC circuit resonates when :
At resonance the impedance is a minimum () and the current is a maximum, in phase with the voltage. The voltages across and are each times the supply voltage.
Worked example. , H, F. Then rad/s, and rad/s.
A parallel resonant circuit has the maximum impedance at resonance and minimum line current.
4. AC power and power factor
For a sinusoidal voltage and current with phase angle :
- Real power (watts).
- Reactive power (VAr).
- Apparent power (VA), with .
- Power factor .
Poor power factor raises current for the same real power, so losses and voltage drop rise. A capacitor bank of reactive size raises the factor from to . For 100 kW at 0.8 lagging corrected to unity, kVAr.
The RMS value of a sine wave is the peak divided by , and the form factor (RMS over average) is 1.11.
5. Three-phase systems
| Connection | Line voltage | Line current |
|---|---|---|
| Star | ||
| Delta |
In either connection, balanced three-phase power is:
A delta load draws three times the power of the same impedances connected in star on the same supply.
The two-wattmeter method measures three-phase power: and . At unity power factor the readings are equal, at 0.5 one reads zero, and below 0.5 one reads negative.
Worked example. Readings 2000 W and 1000 W give W and , so and the power factor is 0.866.
6. Measuring instruments
| Instrument | Works on | Scale | Use |
|---|---|---|---|
| PMMC | Magnet and coil | Linear | DC only |
| Moving iron | Repulsion or attraction of iron | Non-linear, crowded at the start | AC and DC |
| Dynamometer | Two coils | Square-law for ammeter and voltmeter, linear for wattmeter | AC and DC power |
| Induction | Eddy-current torque | Disc rotation | Energy meters |
Extending range: a shunt across the meter takes , so . A series multiplier gives .
Worked example. A meter of and 1 mA full scale becomes a 100 mA ammeter with .
Instrument transformers let standard meters read high AC quantities: a current transformer keeps its secondary nearly short-circuited and must never be opened under load, and a potential transformer works near open circuit.
7. Bridges
A DC Wheatstone bridge balances when and measures medium resistance. AC bridges balance when in both magnitude and phase.
- Maxwell bridge: inductance.
- Hay bridge: inductance of high- coils.
- Schering bridge: capacitance and dielectric loss angle.
- Wien bridge: frequency and capacitance.
- Kelvin double bridge: very low resistance.
Errors are classed as gross, systematic and random, and accuracy is stated as a percentage of full-scale reading, so readings near the bottom of the scale carry a larger percentage error. For that reason an instrument should be read in the upper part of its range.
Common traps
- Using superposition for power. It holds for voltage and current only.
- Assuming 100 percent efficiency at maximum power transfer. It is 50 percent.
- Mixing star and delta relations for line and phase quantities.
- Opening the secondary of a current transformer while the primary carries current.
- Reading a moving-iron scale as linear.
Memory aids
- "RL equals Rth": maximum power.
- "Root three in star voltage, in delta current": three-phase relations.
- "Series resonance minimum Z, parallel maximum Z": resonance.
Summary
Network theorems reduce circuits to a source and a resistance, and transients and resonance follow from time constants and the condition . AC power uses the power triangle, and three-phase work uses star-delta relations and the two-wattmeter method.
Measurements revolve around instrument types, range extension and bridge balance conditions.
Exam protocol
- Reduce to Thevenin first when a single element varies.
- Draw the power triangle for any power-factor question.
- Check star or delta before using a three-phase relation.
- Never open a CT secondary in a safety item.
